Product Description
Introduction of ESD200 Flammable EX LEL VOC Gas Detector
The ESD200 is a high-precision fixed gas detector designed for industrial and commercial environments. It supports detection of flammable gases, toxic gases and VOCs, adopting catalytic combustion, electrochemical and PID detection principles. With stable performance and diverse detection ranges, it meets long-term, continuous gas leakage monitoring needs for multiple scenarios.
Engineered for harsh working conditions, this detector features full certifications and excellent environmental adaptability. It delivers accurate and repeatable detection data, with fast response speed, effectively eliminating potential safety hazards in gas leakage and ensuring operational safety for factories and laboratories.
Feature of ESD200 Flammable EX LEL VOC Gas Detector
1) Multi-gas Compatibility: It detects flammable gases (0-100% LEL), various toxic gases and VOCs, covering 18 common industrial gases to suit diverse monitoring demands.
2) Certified Safety Performance: It obtains professional Ex explosion-proof, CPA metering, fire safety and CE certifications, compliant with national and international industry standards for reliable operation.
3) High Detection Accuracy: It achieves ±3% LEL/±3%FS accuracy and ≤2% repeatability, with T90 response time within 20s for flammable gases, ensuring real-time and precise monitoring.
4) Flexible Communication & Output: Equipped with HART communication and optional 4-20mA signal output, plus 3 groups of alarm/fault relays, it supports seamless connection with industrial control systems.
5) Easy Maintenance & Durability: Adopts replaceable sensor design with long service life. IP66 waterproof and dustproof grade works stably at -40℃ to 70℃ for wide environmental adaptability.
Detail photos of GTYQ-ESD200 Flammable Gas Detector



Product parameters of ESD200 Flammable EX LEL VOC Gas Detector
| Performance | |
| Detectable Gas | Combustible gas / Toxic gas / VOC / Other gases |
| Detection Principle | Catalytic combustion / Electro‑chemical / PID |
| Measurement Range | 0%~100% LEL (combustible gas); see the table below for other gases |
| Accuracy | ±3% LEL (combustible gas) / ±3%FS (toxic gas) |
| Repeatability | ≤ 2 % |
| Response Time | T90 < 20 s (catalytic combustion); see the table below for other principles |
| Electrical Characteristics | |
| Power Consumption | < 2.5 W (combustible gas, without sound‑light alarm); < 1.5 W (toxic gas, without sound‑light alarm) |
| Power Supply | 24 VDC (operating voltage range: 10‑30 VDC) |
| Output Signal | 3‑wire 4‑20 mA / 2‑wire 4‑20 mA (toxic gas); optional HART digital communication; alarm / fault relay: 1A @ 24 VDC (3 groups) |
| Mechanical & Structural Characteristics | |
| Housing Material | ADC12 aluminum alloy / 316 stainless steel |
| Process Thread | M20×1.5, 1/2 NPT internal thread; optional: G3/4, G1/2, 3/4 NPT |
| Weight | 1.5 kg (Al‑alloy, with sound‑light alarm) / 1.42 kg (Al‑alloy, without sound‑light alarm) |
| 3.48 kg (Stainless‑steel, with sound‑light alarm) / 3.4 kg (Stainless‑steel, without sound‑light alarm) | |
| Certifications | |
| Explosion‑proof Certificate |
Exd ⅡC T6 Gb / Ex tD A21 IP66 T80 °C (combustible gas detector) Exd ib ⅡC T6 Gb / Ex tD ibD A21 IP66 T80 °C (toxic gas detector) |
| Fire‑protection Certificate | Fire-product certification |
| Metrology Certification | CPA |
| CE Certificate | CE |
| Applicable Standards | GB15322.1-2019,GB3836.1-2010,GB3836.2-2010,GB3836.4-2010, GB12476.1-2013, GB12476.4-2010,GB12476.5-2013,JJF1368-2012,GB/T 4208-2017 |
| Environmental Operating Conditions | |
| Ingress Protection | IP66 |
| Ambient Temperature | -40 °C~70 °C (combustible gas); ‑20 °C ~ 50 °C (toxic gas) |
| Humidity | 10‑95%RH (non-condensing) |
| Ambient Pressure | 86‑106 kPa |
| Alarm Thresholds (Factory Default) | Low-level alarm: 25%FS; High-level alarm: 50%FS |
| Sensor Service Life | Catalytic sensor: 5 years (in clean atmosphere) |
| Electro-chemical sensor: ≥1 year (in clean atmosphere) | |
| PID lamp: ≥5000 hours (in clean atmosphere) | |
ESD200 Detectable Toxic Gases List
| No. | Gas Name | Chemical Formula | Measurement Range (ppm) | Response Time (s) | Recovery Time (s) | |
| T50 | T90 | T10 | ||||
| 1 | Oxygen | O2 | 0-25%VOL | <10 | <25 | <20 |
| 2 | Carbon monoxide | CO | 0-100/200/500/1000 | <15 | <25 | <45 |
| 3 | Hydrogen sulfide | H2S | 0-20/50/100 | <10 | <30 | <40 |
| 4 | Hydrogen | H2 | 1000 | <20 | <50 | <60 |
| 5 | Ammonia | NH3 | 0-100/500/1000 | <40 | <90 | <120 |
| 6 | Chlorine | CL2 | 0-10/20 | <30 | <50 | <60 |
| 7 | Nitric oxide | NO | 0-100/500 | <10 | <30 | <90 |
| 8 | Nitrogen dioxide | NO2 | 0-20/50 | <40 | <90 | <90 |
| 9 | Sulfur dioxide | SO2 | 0-20/100 | <15 | <40 | <90 |
| 10 | Vinyl chloride | C2H3CL | 0-20/100 | <35 | <90 | <180 |
| 11 | Acrylonitrile | C3H3N | 0-100/200 | <80 | <160 | <180 |
| 12 | Methanol | CH3OH | 0-100/200/500 | <20 | <80 | <150 |
| 13 | Formaldehyde | CH2O | 0-50/100/200/500 | <25 | <70 | <150 |
| 14 | Ethylene oxide | C2H4O | 0-20/100/200 | <50 | <120 | <180 |
| 15 | Hydrogen chloride | HCL | 0-30/50 | <50 | <80 | <120 |
| 16 | Hydrogen fluoride | HF | 0-10 | <30 | <90 | <120 |
| 17 | Hydrogen cyanide | HCN | 0-30 | <40 | <90 | <120 |
| 18 | Tetrahydrothiophene | C4H8S | 0-30 | <20 | <60 | <120 |
FAQ about ESD200 Flammable EX LEL VOC Gas Detector
Q1: What gases can the ESD200 detect?
A1: It covers flammable gases, VOCs and 18 types of toxic gases including CO, H2S, O2, NH3 and formaldehyde.
Q2: Is it suitable for hazardous explosive areas?
A2: Yes. It holds complete Ex explosion-proof certifications, specially designed for flammable and explosive industrial sites.
Q3: What is the working temperature range?
A3: It works from -40℃ to 70℃ for flammable gases and -20℃ to 50℃ for toxic gases, adapting to most industrial environments.
Q4: How about the sensor service life?
A4: Catalytic sensors last 5 years, electrochemical sensors over 1 year, and PID bulbs over 5000 hours in clean environments.
Q5: Does it support real-time on-site viewing?
A5: Yes. Built-in LCD screen displays real-time gas data on-site for intuitive and convenient on-site checking.
English
Español
Português
русский
français
日本語
Deutsch
Tiếng Việt
Italiano
Nederlands
ไทย
Polski
한국어
Svenska
magyar
Malay
বাংলা
Dansk
Suomi
Pilipino
Gaeilge
عربى
norsk
اردو
čeština
Ελληνικά
Українська
فارسی
தமிழ்
తెలుగు
नेपाली
Burmese
български
ລາວ
Latine
Қазақ
Azərbaycan
slovenský
Македонски
Lietuvos
Eesti Keel
Română
Slovenski
Српски
Afrikaans
Беларус
Монгол хэл
O'zbek
Sundanese
Javanese