Product Description
Introduction of Gas Detection for Battery Energy Storage Systems
Battery energy storage systems (BESS) face latent safety risks from battery thermal runaway, where carbon monoxide (CO) leakage is a key early warning sign. The CGT-CO2000 gas detector is professionally engineered for BESS scenarios including energy storage power stations, containers and cabinets. It delivers real-time, continuous CO concentration monitoring to identify early battery abnormalities, trigger graded alarms, and prevent fire and explosion accidents caused by thermal runaway.
Featuring robust industrial adaptability, this explosion-proof detector suits Zone 1/2 hazardous environments and IIA/IIB/IIC gas and dust atmospheres with a T1-T6 temperature rating. It operates stably across extreme temperatures from -40℃ to +70℃ and wide humidity ranges, ensuring reliable 24/7 monitoring for long-term energy storage operation with minimal environmental interference.
Feature of Gas Detection for Battery Energy Storage Systems
1) Long Lifespan & Maintenance-Free Design: Equipped with high-performance electrochemical sensors, it offers a 10-year service life under normal conditions. The factory pre-calibrated design supports free calibration and zero daily maintenance, greatly reducing operational costs.
2) High Precision & Graded Alarm System: It provides accurate detection within 0–2000ppm CO range with 1ppm resolution. Dual-stage alarms (200ppm low alarm, 500ppm high alarm) adopt distinct red light flashing/steady states for intuitive risk judgment.
3) Excellent Explosion-Proof & Protective Performance: With Ex db IIC T6 Gb explosion-proof certification and IP66 waterproof and dustproof rating, the die-cast aluminum shell resists harsh on-site conditions and meets strict hazardous area safety standards.
4) Flexible Networking & Stable Signal Output: Supporting RS485 (9600bps) communication and hand-in-hand networking, it connects up to 32 detectors per bus. Built-in selectable 120Ω terminal resistor and dual dry contact relays ensure stable alarm signal transmission.
5) Wide Environmental Adaptability: It works steadily under 18–32VDC wide voltage input and 86–106kPa atmospheric pressure. Anti-interference circuit design avoids disturbance from power supply and ambient signals for consistent detection accuracy.
Detail photos of Gas Detection for Battery Energy Storage Systems



Product parameters of Gas Detection for Battery Energy Storage Systems
| Type | Specific parameters |
| Appearance parameter | |
| Pigment | dark grey |
| Shell material | die-casting aluminium |
| Outline dimension | approximately 100 mm × 78 mm × 53 mm |
| Product weight | approximately 415 g |
| Function parameter | |
| Test gas | CO(carbon monoxide) |
| Sensor type | electrochemical sensor |
| Sample mode | natural diffusion |
| Detection range | (0~2000)×10-6 (volume fraction) |
| Operate mode | continuous monitoring |
| Alarm value setting range (Two-level alarm) |
The minimum alarm threshold for production output is set at 200×10-6 (volume fraction). The maximum alarm threshold for the outlet concentration is set at 500×10-6 (volume fraction). |
| Alarm error | ±50×10-6 (volume fraction) |
| Range indication deviation | allowable error: ±80×10-6 (volume fraction) |
| Alarming light visibility | > 5 m (in darkness) |
| Response time | ≤ 30s |
| Call time | ≤ 15s |
| Resolution ratio | 1×10-6 (volume fraction) |
| Zero drift range | ≤50×10-6 (volume fraction) |
| Sensor service life | normal monitoring environment for 15 years |
| Electrical parameters | |
| Working voltage | 18VDC-32VDC |
| Rated voltage | 24VDC |
| Power dissipation | ≤ 1W |
| Working current | ≤ 5 mA |
| Alarm current | ≤ 25mA |
| Maximum current | ≤ 25mA |
| Output signal | RS485 (optional) [The communication address defaults to 1 at factory; a built-in 120Ω matching resistor is not connected by default and can be enabled using a jumper cap] |
| Baud rate | 9600 bps |
| Dry contact 1 – Low alarm relay | Group 1: Contact capacity (resistance load): 1A @30VDC; 300 mA @ 125VAC. Factory default: Open during normal operation, close during alarms, open during power loss. |
| Dry contact 2 – High alarm relay | Group 1: Contact capacity (resistance load): 1A @30VDC; 300 mA @ 125VAC. Factory default: Open during normal operation, close during alarms, open during power loss. |
| Indicate way | |
| Pilot lamp | 3 LED status lights |
| State indication | 1. During normal operation: The green indicator light remains illuminated continuously |
| 2. In case of a malfunction: The yellow indicator light remains constantly illuminated. | |
| 3. Alarm indication: When the lower limit is exceeded, a red light flashes; when the upper limit is exceeded, the red light remains on continuously. | |
| 4. During the upgrade process: Red, yellow, and green lights will flash alternately. | |
| Upgrade and configuration parameters | Can be connected to a computer via the RS485 bus (optional) |
| Certification and protection level | |
| Attestation | ROHS, CE ,ATEx, IECEx |
| Protect grade | IP66 |
| Explosion-proof mark |
II2 G Ex db IIC T6 Gb II2 D Ex tb IIIC T80°C Db |
FAQ about Gas Detection for Battery Energy Storage Systems
Q1: Is regular calibration required during use?
A1: No. The detector is fully calibrated before delivery, supporting free calibration and maintenance under normal operating conditions. Periodic testing is only needed after long-term service.
Q2: How many detectors can be networked in one system?
A2: A single RS485 bus can connect up to 32 detectors in hand-in-hand mode. Only one terminal resistor needs to be enabled on the whole network for stable communication.
Q3: What are the alarm status indications?
A3: Green light for normal operation, yellow light for faults, red flashing for low-concentration CO alarms, and red steady light for high-concentration alarms for clear status identification.
Q4: What environments are prohibited for the detector?
A4: Avoid high-concentration CO exposure over 2000ppm, direct water splash, long-term high temperature above 90℃, and contact with silicone, sulfide and volatile organics to prevent permanent sensor damage.
Q5: Who should perform installation and commissioning?
A5: All installation, wiring and debugging must be completed by professional technicians. Live cover opening and wiring operations are strictly prohibited to ensure explosion-proof safety.
English
Español
Português
русский
français
日本語
Deutsch
Tiếng Việt
Italiano
Nederlands
ไทย
Polski
한국어
Svenska
magyar
Malay
বাংলা
Dansk
Suomi
Pilipino
Gaeilge
عربى
norsk
اردو
čeština
Ελληνικά
Українська
فارسی
தமிழ்
తెలుగు
नेपाली
Burmese
български
ລາວ
Latine
Қазақ
Azərbaycan
slovenský
Македонски
Lietuvos
Eesti Keel
Română
Slovenski
Српски
Afrikaans
Беларус
Монгол хэл
O'zbek
Sundanese
Javanese